Provided by: mbpoll_1.4.11+dfsg-2build1_amd64 bug

Presentation

       mbpoll  is  a command line utility to communicate with ModBus slave (RTU or TCP).  It uses
       libmodbus ⟨http://libmodbus.org/⟩.  This is a multiplatform project, the  compilation  was
       tested  on  GNU  Linux  x86  and  x86_64,  Microsoft  Windows  7  x86  and GNU Linux ARM 6
       (Raspbian).  Although the syntax of these options is very close modpoll  proconX  program,
       it is a completely independent project.

       mbpoll can:

       -  read  discrete  inputs  - read and write binary outputs (coil) - read input registers -
       read and write output registers (holding register)

       The reading and writing registers may  be  in  decimal,  hexadecimal  or  floating  single
       precision.

Quickstart guide

       The fastest and safest way to install mbpoll is to use the APT repository from piduino.org
       ⟨http://apt.piduino.org⟩, so you should do the following :

           wget -O- http://www.piduino.org/piduino-key.asc | sudo apt-key add -
           sudo add-apt-repository 'deb http://apt.piduino.org stretch piduino'
           sudo apt update
           sudo apt install mbpoll

       This repository provides mbpoll and libmodbus (version 3.1.4) packages  for  i386,  amd64,
       armhf  and arm64 architectures.  In the above commands, the repository is a Debian Stretch
       distribution, but you can also choose Ubuntu Xenial by replacing stretch with xenial.   It
       may be necessary to install the software-properties-common package for add-apt-repository.

       For Raspbian you have to do a little different :

           wget -O- http://www.piduino.org/piduino-key.asc | sudo apt-key add -
           echo    'deb    http://raspbian.piduino.org    stretch    piduino'    |    sudo    tee
       /etc/apt/sources.list.d/piduino.list
           sudo apt update
           sudo apt install mbpoll

       The Raspbian repository provides Piduino packages for armhf architecture for Stretch only.

Build from source

       For example, for a debian system:

       * Install libmodbus ⟨https://github.com/stephane/libmodbus.git⟩ (Version >= 3.1.4) :

               $ sudo apt-get install build-essential libtool git-core autoconf
               $ git clone https://github.com/stephane/libmodbus.git
               $ cd libmodbus
               $ ./autogen.sh
               $ ./configure
               $ make
               $ sudo make install

       You can also install it with apt if the version of libmodbus is greater than or  equal  to
       3.1.4.  For example to query a debian system:

           $ apt-cache show libmodbus-dev

       *  Install  piduino  ⟨https://github.com/epsilonrt/piduino/tree/dev⟩  only  if you want to
       manage the RS485 with a GPIO signal:

               $ sudo apt-get install cmake libcppdb-dev pkg-config libsqlite3-dev sqlite3
               $ git clone https://github.com/epsilonrt/piduino.git
               $ cd piduino
               $ git checkout dev
               $ mkdir build
               $ cd build
               $ cmake ..
               $ make
               $ sudo make install

       * Generate Makefile with cmake:

               $ sudo apt-get install cmake pkg-config
               $ cd mbpoll
               $ mkdir build
               $ cd build
               $ cmake ..

       * Compile and install mbpoll:

               $ make
               $ sudo make install
               $ sudo ldconfig

       If you prefer, you can in the place of direct compilation create a package and install it:

               $ make package
               $ sudo dpkg -i * .deb

       That's all !

Examples

       The following command is used to read the input registers 1 and 2 of the slave at  address
       33 connected through RTU /dev/ttyUSB2 (38400 Bd)

       ---

               $ mbpoll -a 33 -b 38400 -t 3 -r 1 -c 2 /dev/ttyUSB2

               mbpoll 0.1-10 - FieldTalk(tm) Modbus(R) Master Simulator
               Copyright (c) 2015 epsilonRT, All rights reserved.
               This software is governed by the CeCILL license ⟨http://www.cecill.info⟩

               Protocol configuration: Modbus RTU
               Slave configuration...: address = [33]
                                       start reference = 1, count = 2
               Communication.........: /dev/ttyUSB2, 38400-8E1
                                       t/o 1.00 s, poll rate 1000 ms
               Data type.............: 16-bit register, input register table

               -- Polling slave 33... Ctrl-C to stop)
               [1]:   9997
               [2]:   10034
               -- Polling slave 33... Ctrl-C to stop)
               [1]:   10007
               [2]:   10034
               -- Polling slave 33... Ctrl-C to stop)
               [1]:   10007
               [2]:   10034
               -- Polling slave 33... Ctrl-C to stop)
               [1]:   10007
               [2]:   10034
               ^C--- /dev/ttyUSB2 poll statistics ---
               4 frames transmitted, 4 received, 0 errors, 0.0% frame loss

               everything was closed.
               Have a nice day !

Help

       A complete help is available with the -h option:

           usage : mbpoll [ options ] device|host [ writevalues... ] [ options ]

           ModBus Master Simulator. It allows to read and write in ModBus slave registers
                                    connected by serial (RTU only) or TCP.

           Arguments :
             device        Serial port when using ModBus RTU protocol
                             COM1, COM2 ...              on Windows
                             /dev/ttyS0, /dev/ttyS1 ...  on Linux
                             /dev/ser1, /dev/ser2 ...    on QNX
             host          Host name or dotted IP address when using ModBus/TCP protocol
             writevalues   List of values to be written.
                           If none specified (default) mbpoll reads data.
                           If negative numbers are provided, it will precede the list of
                           data to be written by two dashes ('--'). for example :
                           mbpoll -t4:int /dev/ttyUSB0 -- 123 -1568 8974 -12
           General options :
             -m #          mode (rtu or tcp, TCP is default)
             -a #          Slave address (1-255 for rtu, 0-255 for tcp, 1 is default)
                           for reading, it is possible to give an address list
                           separated by commas or colons, for example :
                           -a 32,33,34,36:40 read [32,33,34,36,37,38,39,40]
             -r #          Start reference (1 is default)
             -c #          Number of values to read (1-125, 1 is default)
             -u            Read the description of the type, the current status, and other
                           information specific to a remote device (RTU only)
             -t 0          Discrete output (coil) data type (binary 0 or 1)
             -t 1          Discrete input data type (binary 0 or 1)
             -t 3          16-bit input register data type
             -t 3:hex      16-bit input register data type with hex display
             -t 3:int      32-bit integer data type in input register table
             -t 3:float    32-bit float data type in input register table
             -t 4          16-bit output (holding) register data type (default)
             -t 4:hex      16-bit output (holding) register data type with hex display
             -t 4:int      32-bit integer data type in output (holding) register table
             -t 4:float    32-bit float data type in output (holding) register table
             -0            First reference is 0 (PDU addressing) instead 1
             -B            Big endian word order for 32-bit integer and float
             -1            Poll only once only, otherwise every poll rate interval
             -l #          Poll rate in ms, ( > 10, 1000 is default)
             -o #          Time-out in seconds (0.01 - 10.00, 1.00 s is default)
           Options for ModBus / TCP :
             -p #          TCP port number (502 is default)
           Options for ModBus RTU :
             -b #          Baudrate (1200-921600, 19200 is default)
             -d #          Databits (7 or 8, 8 for RTU)
             -s #          Stopbits (1 or 2, 1 is default)
             -P #          Parity (none, even, odd, even is default)
             -R [#]        RS-485 mode (/RTS on (0) after sending)
                            Optional parameter for the GPIO RTS pin number
             -F [#]        RS-485 mode (/RTS on (0) when sending)
                            Optional parameter for the GPIO RTS pin number

             -h            Print this help summary page
             -V            Print version and exit
             -v            Verbose mode.  Causes mbpoll to print debugging messages about
                           its progress.  This is helpful in debugging connection...

       --- > Copyright © 2015-2019 Pascal JEAN, All rights reserved.

       > mbpoll is free software: you can redistribute it and/or modify it under the terms of the
       GNU General Public License as published by the Free Software Foundation, either version  3
       of the License, or (at your option) any later version.

       >  mbpoll  is  distributed  in  the hope that it will be useful, but WITHOUT ANY WARRANTY;
       without even the implied warranty of MERCHANTABILITY or FITNESS FOR A PARTICULAR  PURPOSE.
       See the GNU General Public License for more details.

       >  You should have received a copy of the GNU General Public License along with mbpoll. If
       not, see ⟨http://www.gnu.org/licenses/⟩.

                                                                                         mbpoll()