NAME

       ups.conf - UPS definitions for Network UPS Tools

DESCRIPTION

       This file is read by the driver controller upsdrvctl(8), the UPS
       drivers that use the common core (see nutupsdrv(8), and upsd(8)). The
       file begins with global directives, and then each UPS has a section
       which contains a number of directives that set parameters for that UPS.

       A UPS section begins with the name of the UPS in brackets, and
       continues until the next UPS name in brackets or until EOF. The name
       "default" is used internally in upsd, so you can't use it in this file.

       You must define the driver and port elements for each entry. Anything
       after that in a section is optional. A simple example might look like
       this:

           [myups]
                   driver = blazer_ser
                   port = /dev/ttyS0
                   desc = "Web server UPS"

       A slightly more complicated version includes some extras for the
       hardware-specific part of the driver:

           [bigups]
                   driver = apcsmart
                   port = /dev/cua00
                   cable = 940-0095B
                   sdtype = 2
                   desc = "Database server UPS"

       In this case, the apcsmart(8) driver will receive variables called
       "cable" and "sdtype" which have special meanings. See the man pages of
       your driver(s) to learn which variables are supported and what they do.

GLOBAL DIRECTIVES

       chroot
           Optional. The driver will chroot(2) to this directory during
           initialization. This can be useful when securing systems.

       driverpath
           Optional. Path name of the directory in which the UPS driver
           executables reside. If you don't specify this, the programs look in
           a built-in default directory, which is often /usr/local/ups/bin.

       maxstartdelay
           Optional. Same as the UPS field of the same name, but this is the
           default for UPSes that don't have the field.

       pollinterval
           Optional. The status of the UPS will be refreshed after a maximum
           delay which is controlled by this setting. This is normally 2
           seconds. This may be useful if the driver is creating too much of a
           load on your system or network.

       user
           Optional. If started as root, the driver will setuid(2) to the user
           id associated with username.

UPS FIELDS

       driver
           Required. This specifies which program will be monitoring this UPS.
           You need to specify the one that is compatible with your hardware.
           See nutupsdrv(8) for more information on drivers in general and
           pointers to the man pages of specific drivers.

       port
           Required. This is the serial port where the UPS is connected. On a
           Linux system, the first serial port usually is /dev/ttyS0. On
           FreeBSD and similar systems, it probably will be /dev/cuaa0.

       sdorder
           Optional. When you have multiple UPSes on your system, you usually
           need to turn them off in a certain order. upsdrvctl shuts down all
           the 0s, then the 1s, 2s, and so on. To exclude a UPS from the
           shutdown sequence, set this to -1.

           The default value for this parameter is 0.

       desc
           Optional. This allows you to set a brief description that upsd will
           provide to clients that ask for a list of connected equipment.

       nolock
           Optional. When you specify this, the driver skips the port locking
           routines every time it starts. This may allow other processes to
           seize the port if you start more than one accidentally.

           You should only use this if your system won't work without it.

           This may be needed on Mac OS X systems.

       ignorelb
           Optional. When you specify this, the driver ignores a low battery
           condition flag that is reported by the UPS (some devices will
           switch off almost immediately after setting this flag, or will
           report this as soons as the mains fails). Instead it will use
           either of the following conditions to determine when the battery is
           low:

               battery.charge < battery.charge.low
               battery.runtime < battery.runtime.low

           The idea is to set the battery.charge.low and/or
           battery.runtime.low levels in ups.conf to a value that gives enough
           time to cleanly shutdown your system:

               override.battery.charge.low = 30
               override.battery.runtime.low = 180

           In order for this to work, your UPS should be able to (reliably)
           report charge and/or runtime remaining on battery. Use with
           caution!

       maxstartdelay
           Optional. This can be set as a global variable above your first UPS
           definition and it can also be set in a UPS section. This value
           controls how long upsdrvctl will wait for the driver to finish
           starting. This keeps your system from getting stuck due to a broken
           driver or UPS.

           The default is 45 seconds.

       default.<variable>
           Optional. Set a default value for <variable> which is used in case
           the UPS doesn't provide a value, but will be overwritten if a value
           is available from the UPS:

               default.input.voltage.nominal = 230

           The above will report the nominal input voltage to be 230, unless
           the UPS tells us differently.

       override.<variable>
           Optional. Set a value for <value> that overrides any value that may
           be read from the UPS. Used for overriding values from the UPS that
           are clearly wrong (some devices report wrong values for battery
           voltage for instance):

               override.battery.voltage.nominal = 12

           Use with caution! This will only change the appearance of the
           variable to the outside world, internally in the UPS the original
           value is used.

       All other fields are passed through to the hardware-specific part of
       the driver. See those manuals for the list of what is allowed.

INTEGRATION

       upsdrvctl(8) uses this file to start and stop the drivers.

       The drivers themselves also obtain configuration data from this file.
       Each driver looks up its section and uses that to configure itself.

       upsd(8) learns about which UPSes are installed on this system by
       reading this file. If this system is called "doghouse" and you have
       defined a UPS in your ups.conf called "snoopy", then you can monitor it
       from upsc(8) or similar as "snoopy@doghouse".