Provided by: nut-client_2.7.4-5.1ubuntu2_amd64 bug

NAME

       upsmon.conf - Configuration for Network UPS Tools upsmon

DESCRIPTION

       This file’s primary job is to define the systems that upsmon(8) will monitor and to tell
       it how to shut down the system when necessary. It will contain passwords, so keep it
       secure. Ideally, only the upsmon process should be able to read it.

       Additionally, other optional configuration values can be set in this file.

CONFIGURATION DIRECTIVES

       DEADTIME seconds
           upsmon allows a UPS to go missing for this many seconds before declaring it "dead".
           The default is 15 seconds.

           upsmon requires a UPS to provide status information every few seconds (see POLLFREQ
           and POLLFREQALERT) to keep things updated. If the status fetch fails, the UPS is
           marked stale. If it stays stale for more than DEADTIME seconds, the UPS is marked
           dead.

           A dead UPS that was last known to be on battery is assumed to have changed to a low
           battery condition. This may force a shutdown if it is providing a critical amount of
           power to your system. This seems disruptive, but the alternative is barreling ahead
           into oblivion and crashing when you run out of power.

           Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT. Otherwise, you’ll
           have "dead" UPSes simply because upsmon isn’t polling them quickly enough. Rule of
           thumb: take the larger of the two POLLFREQ values, and multiply by 3.

       FINALDELAY seconds
           When running in master mode, upsmon waits this long after sending the NOTIFY_SHUTDOWN
           to warn the users. After the timer elapses, it then runs your SHUTDOWNCMD. By default
           this is set to 5 seconds.

           If you need to let your users do something in between those events, increase this
           number. Remember, at this point your UPS battery is almost depleted, so don’t make
           this too big.

           Alternatively, you can set this very low so you don’t wait around when it’s time to
           shut down. Some UPSes don’t give much warning for low battery and will require a value
           of 0 here for a safe shutdown.

               Note
               If FINALDELAY on the slave is greater than HOSTSYNC on the master, the master will
               give up waiting for the slave to disconnect.

       HOSTSYNC seconds
           upsmon will wait up to this many seconds in master mode for the slaves to disconnect
           during a shutdown situation. By default, this is 15 seconds.

           When a UPS goes critical (on battery + low battery, or "FSD": forced shutdown), the
           slaves are supposed to disconnect and shut down right away. The HOSTSYNC timer keeps
           the master upsmon from sitting there forever if one of the slaves gets stuck.

           This value is also used to keep slave systems from getting stuck if the master fails
           to respond in time. After a UPS becomes critical, the slave will wait up to HOSTSYNC
           seconds for the master to set the FSD flag. If that timer expires, the slave will
           assume that the master is broken and will shut down anyway.

           This keeps the slaves from shutting down during a short-lived status change to "OB LB"
           that the slaves see but the master misses.

       MINSUPPLIES num
           Set the number of power supplies that must be receiving power to keep this system
           running. Normal computers have just one power supply, so the default value of 1 is
           acceptable.

           Large/expensive server type systems usually have more, and can run with a few missing.
           The HP NetServer LH4 can run with 2 out of 4, for example, so you’d set it to 2. The
           idea is to keep the box running as long as possible, right?

           Obviously you have to put the redundant supplies on different UPS circuits for this to
           make sense! See big-servers.txt in the docs subdirectory for more information and
           ideas on how to use this feature.

           Also see the section on "power values" in upsmon(8).

       MONITOR system powervalue username password type
           Each UPS that you need to be monitor should have a MONITOR line. Not all of these need
           supply power to the system that is running upsmon. You may monitor other systems if
           you want to be able to send notifications about status changes on them.

       You must have at least one MONITOR directive in upsmon.conf.

       system is a UPS identifier. It is in this form:

       <upsname>[@<hostname>[:<port>]]

       The default hostname is "localhost". Some examples:

       •   "su700@mybox" means a UPS called "su700" on a system called "mybox". This is the
           normal form.

       •   "fenton@bigbox:5678" is a UPS called "fenton" on a system called "bigbox" which runs
           upsd(8) on port "5678".

       powervalue is an integer representing the number of power supplies that the UPS feeds on
       this system. Most normal computers have one power supply, and the UPS feeds it, so this
       value will be 1. You need a very large or special system to have anything higher here.

       You can set the powervalue to 0 if you want to monitor a UPS that doesn’t actually supply
       power to this system. This is useful when you want to have upsmon do notifications about
       status changes on a UPS without shutting down when it goes critical.

       The username and password on this line must match an entry in that system’s upsd.users(5).
       If your username is "monmaster" and your password is "blah", the MONITOR line might look
       like this:

       MONITOR myups@bigserver 1 monmaster blah master

       Meanwhile, the upsd.users on bigserver would look like this:

           [monmaster]
                   password  = blah
                   upsmon master #  (or slave)

       The type refers to the relationship with upsd(8). It can be either "master" or "slave".
       See upsmon(8) for more information on the meaning of these modes. The mode you pick here
       also goes in the upsd.users file, as seen in the example above.

       NOCOMMWARNTIME seconds
           upsmon will trigger a NOTIFY_NOCOMM after this many seconds if it can’t reach any of
           the UPS entries in this configuration file. It keeps warning you until the situation
           is fixed. By default this is 300 seconds.

       NOTIFYCMD command
           upsmon calls this to send messages when things happen.

           This command is called with the full text of the message as one argument. The
           environment string NOTIFYTYPE will contain the type string of whatever caused this
           event to happen.

           If you need to use upssched(8), then you must make it your NOTIFYCMD by listing it
           here.

           Note that this is only called for NOTIFY events that have EXEC set with NOTIFYFLAG.
           See NOTIFYFLAG below for more details.

           Making this some sort of shell script might not be a bad idea. For more information
           and ideas, see docs/scheduling.txt

           Remember, this command also needs to be one element in the configuration file, so if
           your command has spaces, then wrap it in quotes.

           NOTIFYCMD "/path/to/script --foo --bar"

           This script is run in the background—that is, upsmon forks before it calls out to
           start it. This means that your NOTIFYCMD may have multiple instances running
           simultaneously if a lot of stuff happens all at once. Keep this in mind when designing
           complicated notifiers.

       NOTIFYMSG type message
           upsmon comes with a set of stock messages for various events. You can change them if
           you like.

               NOTIFYMSG ONLINE "UPS %s is getting line power"

               NOTIFYMSG ONBATT "Someone pulled the plug on %s"

           Note that %s is replaced with the identifier of the UPS in question.

           The message must be one element in the configuration file, so if it contains spaces,
           you must wrap it in quotes.

               NOTIFYMSG NOCOMM "Someone stole UPS %s"

           Possible values for type:

           ONLINE
               UPS is back online

           ONBATT
               UPS is on battery

           LOWBATT
               UPS is on battery and has a low battery (is critical)

           FSD
               UPS is being shutdown by the master (FSD = "Forced Shutdown")

           COMMOK
               Communications established with the UPS

           COMMBAD
               Communications lost to the UPS

           SHUTDOWN
               The system is being shutdown

           REPLBATT
               The UPS battery is bad and needs to be replaced

           NOCOMM
               A UPS is unavailable (can’t be contacted for monitoring)

       NOTIFYFLAG type flag[+flag][+flag]...
           By default, upsmon sends walls global messages to all logged in users) via /bin/wall
           and writes to the syslog when things happen. You can change this.

           Examples:

               NOTIFYFLAG ONLINE SYSLOG
               NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC

           Possible values for the flags:

           SYSLOG
               Write the message to the syslog

           WALL
               Write the message to all users with /bin/wall

           EXEC
               Execute NOTIFYCMD (see above) with the message

           IGNORE
               Don’t do anything

               If you use IGNORE, don’t use any other flags on the same line.

       POLLFREQ seconds
           Normally upsmon polls the upsd(8) server every 5 seconds. If this is flooding your
           network with activity, you can make it higher. You can also make it lower to get
           faster updates in some cases.

           There are some catches. First, if you set the POLLFREQ too high, you may miss
           short-lived power events entirely. You also risk triggering the DEADTIME (see above)
           if you use a very large number.

           Second, there is a point of diminishing returns if you set it too low. While upsd
           normally has all of the data available to it instantly, most drivers only refresh the
           UPS status once every 2 seconds. Polling any more than that usually doesn’t get you
           the information any faster.

       POLLFREQALERT seconds
           This is the interval that upsmon waits between polls if any of its UPSes are on
           battery. You can use this along with POLLFREQ above to slow down polls during normal
           behavior, but get quicker updates when something bad happens.

           This should always be equal to or lower than the POLLFREQ value. By default it is also
           set 5 seconds.

           The warnings from the POLLFREQ entry about too-high and too-low values also apply
           here.

       POWERDOWNFLAG filename
           upsmon creates this file when running in master mode when the UPS needs to be powered
           off. You should check for this file in your shutdown scripts and call upsdrvctl
           shutdown if it exists.

           This is done to forcibly reset the slaves, so they don’t get stuck at the "halted"
           stage even if the power returns during the shutdown process. This usually does not
           work well on contact-closure UPSes that use the genericups driver.

           See the config-notes.txt file in the docs subdirectory for more information. Refer to
           the section:

           "Configuring automatic shutdowns for low battery events", or refer to the online
           version.

       RBWARNTIME seconds
           When a UPS says that it needs to have its battery replaced, upsmon will generate a
           NOTIFY_REPLBATT event. By default, this happens every 43200 seconds (12 hours).

           If you need another value, set it here.

       RUN_AS_USER username
           upsmon normally runs the bulk of the monitoring duties under another user ID after
           dropping root privileges. On most systems this means it runs as "nobody", since that’s
           the default from compile-time.

           The catch is that "nobody" can’t read your upsmon.conf, since by default it is
           installed so that only root can open it. This means you won’t be able to reload the
           configuration file, since it will be unavailable.

           The solution is to create a new user just for upsmon, then make it run as that user. I
           suggest "nutmon", but you can use anything that isn’t already taken on your system.
           Just create a regular user with no special privileges and an impossible password.

           Then, tell upsmon to run as that user, and make upsmon.conf readable by it. Your
           reloads will work, and your config file will stay secure.

           This file should not be writable by the upsmon user, as it would be possible to
           exploit a hole, change the SHUTDOWNCMD to something malicious, then wait for upsmon to
           be restarted.

       SHUTDOWNCMD command
           upsmon runs this command when the system needs to be brought down. If it is a slave,
           it will do that immediately whenever the current overall power value drops below the
           MINSUPPLIES value above.

           When upsmon is a master, it will allow any slaves to log out before starting the local
           shutdown procedure.

           Note that the command needs to be one element in the config file. If your shutdown
           command includes spaces, then put it in quotes to keep it together, i.e.:

               SHUTDOWNCMD "/sbin/shutdown -h +0"

       CERTPATH certificate file or database
           When compiled with SSL support, you can enter the certificate path here.

           With NSS:
               Certificates are stored in a dedicated database (splitted in 3 files). Specify the
               path of the database directory.

           With OpenSSL:
               Directory containing CA certificates in PEM format, used to verify the server
               certificate presented by the upsd server. The files each contain one CA
               certificate. The files are looked up by the CA subject name hash value, which must
               hence be available.

       CERTIDENT certificate name database password
           When compiled with SSL support with NSS, you can specify the certificate name to
           retrieve from database to authenticate itself and the password required to access
           certificate related private key.

       CERTHOST hostname certificate name certverify forcessl
           When compiled with SSL support with NSS, you can specify security directive for each
           server you can contact.

           Each entry maps server name with the expected certificate name and flags indicating if
           the server certificate is verified and if the connection must be secure.

       CERTVERIFY 0 | 1
           When compiled with SSL support, make upsmon verify all connections with certificates.

           Without this, there is no guarantee that the upsd is the right host. Enabling this
           greatly reduces the risk of man-in-the-middle attacks. This effectively forces the use
           of SSL, so don’t use this unless all of your upsd hosts are ready for SSL and have
           their certificates in order.

           When compiled with NSS support of SSL, can be overriden for host specified with a
           CERTHOST directive.

       FORCESSL 0 | 1
           When compiled with SSL, specify that a secured connection must be used to communicate
           with upsd.

           If you don’t use CERTVERIFY 1, then this will at least make sure that nobody can sniff
           your sessions without a large effort. Setting this will make upsmon drop connections
           if the remote upsd doesn’t support SSL, so don’t use it unless all of them have it
           running.

           When compiled with NSS support of SSL, can be overriden for host specified with a
           CERTHOST directive.

SEE ALSO

       upsmon(8), upsd(8), nutupsdrv(8).

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/