NAME

       apcsmart-old - Driver for American Power Conversion Smart Protocol UPS equipment

SYNOPSIS

       apcsmart-old -h

       apcsmart-old -a UPS_NAME [OPTIONS]

           Note
           This man page only documents the hardware-specific features of the apcsmart-old driver. For
           information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE

       apcsmart-old should recognize all recent APC models that use a serial protocol at 2400 bps. This is
       primarily the Smart-UPS, Matrix-UPS and Back-UPS Pro lines.

       The driver attempts to support every bell and whistle of the APC reporting interface, whether or not this
       is strictly sensible.

       Some older hardware may only report a handful of variables. This is usually not a bug—they just don’t
       support anything else.

CABLING

       This driver expects to see a 940-0024C cable or a clone by default. You can switch to the 940-0095B
       dual-mode cable support with the cable= definition described below.

       If your 940-0024C cable is broken or missing, use this diagram to build a clone:

       http://www.networkupstools.org/cables/940-0024C.jpg

EXTRA ARGUMENTS

       This driver supports the following optional settings in the ups.conf(5):

       cable=940-0095B
           Configure the serial port for the APC 940-0095B dual-mode cable.

       sdtype=num
           Use shutdown type num, according to this table:

           0
               soft shutdown or powerdown, depending on battery status

           1
               soft shutdown followed by powerdown

           2
               instant power off

           3
               power off with grace period

           4
               "force OB" hack method for CS 350

       Modes 0 and 1 will power up the load when power returns. Modes 2 and 3 will keep the load turned off when
       the power returns.

       Mode 4 exploits an oddity in the CS 350 models since they only seem to support the S command, but then
       only when running on battery. As a result, the driver will force the UPS to go on battery if necessary
       before sending the shutdown command. This ensures that the load gets reset.

BUGS

       Some older APC UPS models return bogus data in the status register during a front panel test. This is
       usually detected and discarded, but some other unexpected values have occasionally slipped through.

       APC UPS models with both USB and serial ports require a power cycle when switching from USB communication
       to serial, and perhaps vice versa.

AUTHOR

       Nigel Metheringham <Nigel.Metheringham@Intechnology.co.uk> (drawing heavily on the original apcsmart
       driver by Russell Kroll). This driver was called newapc for a time and was renamed in the 1.5 series. In
       2.6.2 the driver was renamed to apcsmart-old, being superseded by updated version with new features.