Provided by: nut-server_2.8.0-7_amd64 bug

NAME

       microsol-apc - Driver for APC Back-UPS BR UPS equipment

NOTE

       This man page only documents the hardware-specific features of the microsol-apc driver.
       For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE

       This driver supports the following UPS models:

       •   APC Back-UPS BZ1500-BR

       •   APC Back-UPS BZ2200I-BR

       •   APC Back-UPS BZ2200BI-BR

       In 2009, Schneider Electric acquired Microsol Technologies, and by 2012, the entire
       Microsol line was being sold under the APC brand. This driver supports these newer,
       APC-branded models. Older equipment should use solis(8).

EXTRA ARGUMENTS

       This driver support the following extra optional settings in the ups.conf(5).

       battext = n - (default = 0, no extra battery, where n = Ampere*hour )

       prgshut = 1 - (default = 0, no programmable shutdown )

COMMANDS

       •   shutdown.return - Shut down in .3 minutes and restart in .3 minutes

       •   shutdown.stayoff - Shut down in .3 minutes and do not return

ISSUES

       For other APC-Microsol models, the reported voltages, currents and power will be
       incorrect, as the communication protocol reports unprocessed data instead of real values,
       needing model-specific post-processing by the driver. Monitoring of UPS state
       (on-battery/on-line, critical battery) should work for other models, but is untested.

AUTHORS

       •   Ygor A. S. Regados <ygorre@tutanota.com>

       •   Roberto P. Velloso <rvelloso@gmail.com>

       •   Silvino B. Magalhães <sbm2yk@gmail.com>

SEE ALSO

   The core driver:
       nutupsdrv(8)

   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/