Provided by: mbpoll_1.4.11+dfsg-2_amd64 bug

Presentation

       mbpoll is a command line utility to communicate with ModBus slave (RTU or TCP).
       It uses libmodbus ⟨http://libmodbus.org/⟩.
       This  is  a multiplatform project, the compilation was tested on GNU Linux x86 and x86_64,
       Microsoft Windows 7 x86 and GNU Linux ARM 6 (Raspbian).
       Although the syntax of these options is very  close  modpoll  proconX  program,  it  is  a
       completely independent project.

       mbpoll can:

              • read discrete inputs

              • read and write binary outputs (coil)

              • read input registers

              • read and write output registers (holding register)

       The  reading  and  writing  registers  may  be  in decimal, hexadecimal or floating single
       precision.

Quickstart guide

       The fastest and safest way to install mbpoll is to use the APT repository from piduino.org
       ⟨http://apt.piduino.org⟩, so you should do the following :

              wget -O- http://www.piduino.org/piduino-key.asc | sudo apt-key add -
              sudo add-apt-repository 'deb http://apt.piduino.org stretch piduino'
              sudo apt update
              sudo apt install mbpoll

       This  repository  provides  mbpoll and libmodbus (version 3.1.4) packages for i386, amd64,
       armhf and arm64 architectures.  In the above commands, the repository is a Debian  Stretch
       distribution, but you can also choose Ubuntu Xenial by replacing stretch with xenial.
       It   may   be   necessary   to   install   the   software-properties-common   package  for
       add-apt-repository.

       For Raspbian you have to do a little different :

              wget -O- http://www.piduino.org/piduino-key.asc | sudo apt-key add -
              echo 'deb http://raspbian.piduino.org stretch piduino' | sudo tee /etc/apt/sources.list.d/piduino.list
              sudo apt update
              sudo apt install mbpoll

       The Raspbian repository provides Piduino packages for armhf architecture for Stretch only.

Build from source

       For example, for a debian system:

              •

              Install libmodbus ⟨https://github.com/stephane/libmodbus.git⟩ (Version >= 3.1.4) :

                     $ sudo apt-get install build-essential libtool git-core autoconf
                     $ git clone https://github.com/stephane/libmodbus.git
                     $ cd libmodbus
                     $ ./autogen.sh
                     $ ./configure
                     $ make
                     $ sudo make install

       You can also install it with apt if the version of libmodbus is greater than or  equal  to
       3.1.4.  For example to query a debian system:

              $ apt-cache show libmodbus-dev

              •

              Install piduino ⟨https://github.com/epsilonrt/piduino/tree/dev⟩ only if you want to
              manage the RS485 with a GPIO signal:

                     $ sudo apt-get install cmake libcppdb-dev pkg-config libsqlite3-dev sqlite3
                     $ git clone https://github.com/epsilonrt/piduino.git
                     $ cd piduino
                     $ git checkout dev
                     $ mkdir build
                     $ cd build
                     $ cmake ..
                     $ make
                     $ sudo make install

              •

              Generate Makefile with cmake:

                     $ sudo apt-get install cmake pkg-config
                     $ cd mbpoll
                     $ mkdir build
                     $ cd build
                     $ cmake ..

              •

              Compile and install mbpoll:

                     $ make
                     $ sudo make install
                     $ sudo ldconfig

       If you prefer, you can in the place of direct compilation create a package and install it:

                  $ make package
                  $ sudo dpkg -i * .deb

       That's all !

Examples

       The following command is used to read the input registers 1 and 2 of the slave at  address
       33 connected through RTU /dev/ttyUSB2 (38400 Bd)

_________________________________________________________________________________________________

                  $ mbpoll -a 33 -b 38400 -t 3 -r 1 -c 2 /dev/ttyUSB2

                  mbpoll 0.1-10 - FieldTalk(tm) Modbus(R) Master Simulator
                  Copyright (c) 2015 epsilonRT, All rights reserved.
                  This software is governed by the CeCILL license <http://www.cecill.info>

                  Protocol configuration: Modbus RTU
                  Slave configuration...: address = [33]
                                          start reference = 1, count = 2
                  Communication.........: /dev/ttyUSB2, 38400-8E1
                                          t/o 1.00 s, poll rate 1000 ms
                  Data type.............: 16-bit register, input register table

                  -- Polling slave 33... Ctrl-C to stop)
                  [1]:    9997
                  [2]:    10034
                  -- Polling slave 33... Ctrl-C to stop)
                  [1]:    10007
                  [2]:    10034
                  -- Polling slave 33... Ctrl-C to stop)
                  [1]:    10007
                  [2]:    10034
                  -- Polling slave 33... Ctrl-C to stop)
                  [1]:    10007
                  [2]:    10034
                  ^C--- /dev/ttyUSB2 poll statistics ---
                  4 frames transmitted, 4 received, 0 errors, 0.0% frame loss

                  everything was closed.
                  Have a nice day !

Help

       A complete help is available with the -h option:

              usage : mbpoll [ options ] device|host [ writevalues... ] [ options ]

              ModBus Master Simulator. It allows to read and write in ModBus slave registers
                                       connected by serial (RTU only) or TCP.

              Arguments :
                device        Serial port when using ModBus RTU protocol
                                COM1, COM2 ...              on Windows
                                /dev/ttyS0, /dev/ttyS1 ...  on Linux
                                /dev/ser1, /dev/ser2 ...    on QNX
                host          Host name or dotted IP address when using ModBus/TCP protocol
                writevalues   List of values to be written.
                              If none specified (default) mbpoll reads data.
                              If negative numbers are provided, it will precede the list of
                              data to be written by two dashes ('--'). for example :
                              mbpoll -t4:int /dev/ttyUSB0 -- 123 -1568 8974 -12
              General options :
                -m #          mode (rtu or tcp, TCP is default)
                -a #          Slave address (1-255 for rtu, 0-255 for tcp, 1 is default)
                              for reading, it is possible to give an address list
                              separated by commas or colons, for example :
                              -a 32,33,34,36:40 read [32,33,34,36,37,38,39,40]
                -r #          Start reference (1 is default)
                -c #          Number of values to read (1-125, 1 is default)
                -u            Read the description of the type, the current status, and other
                              information specific to a remote device (RTU only)
                -t 0          Discrete output (coil) data type (binary 0 or 1)
                -t 1          Discrete input data type (binary 0 or 1)
                -t 3          16-bit input register data type
                -t 3:hex      16-bit input register data type with hex display
                -t 3:int      32-bit integer data type in input register table
                -t 3:float    32-bit float data type in input register table
                -t 4          16-bit output (holding) register data type (default)
                -t 4:hex      16-bit output (holding) register data type with hex display
                -t 4:int      32-bit integer data type in output (holding) register table
                -t 4:float    32-bit float data type in output (holding) register table
                -0            First reference is 0 (PDU addressing) instead 1
                -B            Big endian word order for 32-bit integer and float
                -1            Poll only once only, otherwise every poll rate interval
                -l #          Poll rate in ms, ( > 10, 1000 is default)
                -o #          Time-out in seconds (0.01 - 10.00, 1.00 s is default)
              Options for ModBus / TCP :
                -p #          TCP port number (502 is default)
              Options for ModBus RTU :
                -b #          Baudrate (1200-921600, 19200 is default)
                -d #          Databits (7 or 8, 8 for RTU)
                -s #          Stopbits (1 or 2, 1 is default)
                -P #          Parity (none, even, odd, even is default)
                -R [#]        RS-485 mode (/RTS on (0) after sending)
                               Optional parameter for the GPIO RTS pin number
                -F [#]        RS-485 mode (/RTS on (0) when sending)
                               Optional parameter for the GPIO RTS pin number

                -h            Print this help summary page
                -V            Print version and exit
                -v            Verbose mode.  Causes mbpoll to print debugging messages about
                              its progress.  This is helpful in debugging connection...

_________________________________________________________________________________________________

              Copyright © 2015-2019 Pascal JEAN, All rights reserved.

              mbpoll  is  free software: you can redistribute it and/or modify it under the terms
              of the GNU General Public License as published by  the  Free  Software  Foundation,
              either version 3 of the License, or (at your option) any later version.

              mbpoll is distributed in the hope that it will be useful, but WITHOUT ANY WARRANTY;
              without even the implied warranty of MERCHANTABILITY or FITNESS  FOR  A  PARTICULAR
              PURPOSE.  See the GNU General Public License for more details.

              You  should  have  received  a  copy  of  the GNU General Public License along with
              mbpoll. If not, see ⟨http://www.gnu.org/licenses/⟩.

                                                                                         mbpoll()