Provided by: owfs-doc_3.2p4+dfsg1-4.3build2_all bug

NAME

       EDS - Embedded Data Systems Sensors

       EDS0064
              - Temperature

       EDS0065
              - Temperature and Humidity

       EDS0066
              - Temperature and Barometric Pressure

       EDS0067
              - Temperature and Light

       EDS0068
              - Temperature, Barometric Pressure and Light

       EDS0070
              - Vibration

       EDS0071
              - RTD 4-wire temperature

       EDS0072
              - RTD 3-wire temperature

       EDS0080
              - 8 Channel Analog Current Input

       EDS0082
              - 8 Channel Analog Voltage Input

       EDS0083
              - 4 Channel Analog Current Input

       EDS0085
              - 4 Channel Analog Voltage Input

       EDS0090
              - 8 Discrete I/O

SYNOPSIS

       Embedded Data Systems microprocessor-based sensors

   Sub-type ( all )
       7E [.]XXXXXXXXXXXX[XX][/[ device_id | device_type | tag ]]

   Memory ( all )
       7E [.]XXXXXXXXXXXX[XX][/[ memory | pages/page.[0-2|ALL] ]]

   Standard ( all )
       7E  [.]XXXXXXXXXXXX[XX][/[  address | crc8 | id | locator | r_address | r_id | r_locator |
       type ]]

   Temperature ( EDS0064/5/6/7/8 )
       7E.XXXXXXXXXXXX/EDS006X  [/[  temperature  |  counters/seconds  |  alarm/temp_[hi|low]   |
       alarm/clear | set_alarm/temp_[hi|low] | threshold/temp_[hi|low] ]]

   Humidity ( EDS0065/8 )
       7E.XXXXXXXXXXXX/EDS006X   [/[   humidity   |   humidex   |   dew_point   |   heat_index  |
       alarm/humidity_[hi|low]   |   alarm/humidex_[hi|low]    |    alarm/dew_point_[hi|low]    |
       alarm/heat_index_[hi|low]     |     alarm/clear     |     set_alarm/humidity_[hi|low]    |
       set_alarm/humidex_[hi|low] | set_alarm/dew_point_[hi|low] |  set_alarm/heat_index_[hi|low]
       | threshold/humidity_[hi|low] |
       threshold/humidex_[hi|low]  | threshold/dew_point_[hi|low] | threshold/heat_index_[hi|low]
       ]]

   Barometric Pressure ( EDS0066/8 )
       7E.XXXXXXXXXXXX/EDS006X   [/[   pressure    |    inHg    |    alarm/pressure_[hi|low]    |
       alarm/inHg_[hi|low]  | alarm/clear | set_alarm/pressure_[hi|low] | set_alarm/inHg_[hi|low]
       | threshold/pressure_[hi|low] | threshold/inHg_[hi|low] ]]

   Light ( EDS0067/8 )
       7E.XXXXXXXXXXXX/EDS006X   [/[   light   |    alarm/light_[hi|low]    |    alarm/clear    |
       set_alarm/light_[hi|low] | threshold/light_[hi|low] ]]

   Vibration ( EDS0070 )
       7E.XXXXXXXXXXXX/EDS0070  [/[  vib_level | vib_peak | vib_min | vib_max | counter/seconds |
       alarm/vib_[hi|low] | alarm/clear | set_alarm/vib_[hi|low] | threshold/vib_[hi|low] ]]

   RTD Temperature ( EDS0071/2 )
       7E.XXXXXXXXXXXX/EDS007X [/[  temperature  |  resistance  |  raw  |  delay  |  user_byte  |
       calibration/[key|constant]    |    counter/[seconds|samples]   |   alarm/temp_[hi|low]   |
       alarm/RTD_[hi_low] | alarm/clear  |  set_alarm/temp_[hi|low]  |  set_alarm/RTD_[hi_low]  |
       threshold/temp_[hi|low] | threshold/RTD_[hi_low] ]]

   Analog Current ( EDS0080 [0-7] EDS0083 [0-3] )
       7E.XXXXXXXXXXXX/EDS0080     [/[     current.[0-7|ALL]     |     max_current.[0-7|ALL]    |
       min_current.[0-7|ALL] | threshold/current_hi.[0-7|ALL] | threshold/current_low.[0-7|ALL] |
       alarm/current_hi.[0-7|ALL|BYTE]         |        alarm/current_low.[0-7|ALL|BYTE]        |
       set_alarm/current_hi.[0-7|ALL|BYTE]     |      set_alarm/current_low.[0-7|ALL|BYTE]      |
       counter/seconds | memory | pages/page.[0-4|ALL]

   Analog Voltage ( EDS0082 [0-7] EDS0085 [0-3] )
       7E.XXXXXXXXXXXX/EDS0082  [/[ volts.[0-7|ALL] | max_volts.[0-7|ALL] | min_volts.[0-7|ALL] |
       threshold/volts_hi.[0-7|ALL]          |          threshold/volts_low.[0-7|ALL]           |
       alarm/volts_hi.[0-7|ALL|BYTE]          |          alarm/volts_low.[0-7|ALL|BYTE]         |
       set_alarm/volts_hi.[0-7|ALL|BYTE] | set_alarm/volts_low.[0-7|ALL|BYTE] | counter/seconds |
       memory | pages/page.[0-4|ALL]

   I/O ( EDS0090 )
       7E.XXXXXXXXXXXX/EDS009X       [/[      input.[0-7|ALL]      |      counter/[seconds      |
       pulses.[0-7|ALL]|reset.[0-7|ALL|BYTE]]                                                   |
       output/[set.[0-7|ALL|BYTE]|off.[0-7|ALL|BYTE]|reset.[0-7|ALL|BYTE]]                      |
       latch/[state.[0-7|ALL|BYTE]|reset.[0-7|ALL|BYTE]]                                        |
       alarm/[hi.[0-7|ALL]|low.[0-7|ALL]|clear] | set_alarm/[hi.[0-7|ALL]|low.[0-7|ALL]]

   LED ( all )
       7E.XXXXXXXXXXXX/EDS00XX/LED/[state|control]

   relay ( all )
       7E.XXXXXXXXXXXX/EDS00XX/relay/[state|control]

FAMILY CODE

       7E

TEMPERATURE

   EDS006X/temperature
       read-only, floating-point
       Temperature  for  the  EDS006X  series  of  chips. In the -55C to 125C range, with 0.0636C
       precision. The temperature is read every second, continually. Data  is  presented  in  the
       specified temperature scale, Celsius by default.

   EDS007X/temperature
       read-only, floating-point
       Temperature  for  the EDS007X series of chips. Read using a wide-range precise RTD sensor.
       Typical range is -60C to 260C with 0.15C accuracy, although a range of -200C  to  850C  is
       possible.  The  temperature  is  read every second unless a longer EDS007X/delay is given.
       Data is presented in the specified temperature scale, Celsius by default.

   EDS007X/resistance
       read-only, floating-point
       Actual measured resistance (Ohms) of the RTD element. Useful if the  RTD  element  doesn't
       conform to the typical European IEC 60751 standard.

HUMIDITY

   EDS006X/humidity
       read-only, floating-point
       Relative humidity in the 0-100 range (percent). Read every 0.2 seconds.

   EDS006X/dew_point
       read-only, floating-point
       Dew  point  computed  from  EDS006X/temperature  and EDS006X/humidity computered every 0.2
       seconds. Data is a calculated temperature and is reported  in  the  specified  temperature
       scale. Default Celsius.

   EDS006X/heat_index
       read-only, floating-point
       Heat  index  computed  from  EDS006X/temperature and EDS006X/humidity computered every 0.2
       seconds. Data is a calculated temperature and is reported  in  the  specified  temperature
       scale. Default Celsius.

   EDS006X/humidex
       read-only, floating-point
       Humidex  (popular  in  Canada)  computed  from  EDS006X/temperature  and  EDS006X/humidity
       computed every 0.2 seconds. Data is a percent and reported in the 0-100 range.

LIGHT

   EDS006X/light
       read-only, unsigned integer
       Ambient light in Lux. Measured every 0.2 seconds.

PRESSURE

   EDS006X/pressure
       read-only, floating-point
       Ambient pressure, measured every 0.2 seconds. Data in the selected pressure scale (default
       mBar).

   EDS006X/inHg
       read-only, floating-point
       Ambient pressure, measured every 0.2 seconds. Data in the inHg scale.

VIBRATION

   EDS0070/vib_level
       read_only, unsigned integer
       Vibration registered by sensor (instantaneous value) in 0-1023 range.

   EDS0070/vib_peak
       read_only, unsigned integer
       Vibration registered by sensor (highest recent value -- slowly decays) in 0-1023 range.

   EDS0070/vib_min
       read_only, unsigned integer
       Vibration registered by sensor (lowest value) in 0-1023 range.

   EDS0070/vib_max
       read_only, unsigned integer
       Vibration registered by sensor (highest value) in 0-1023 range.

CURRENT

       The  EDS0080  and  EDS0083  measure  current in the 4-20mA range, with upper and threshold
       limits and the ability to set an alarm and independently trigger a relay if the  value  is
       out of range.

   EDS0080/current.[0-7|ALL] EDS0083/current.[0-3|ALL]
       read-only, floating point
       Current current level. (4-20mA)

   EDS0080/max_current.[0-7|ALL] EDS0080/max_current.[0-3|ALL]
   EDS0083/min_current.[0-7|ALL] EDS0083/min_current.[0-3|ALL]
       read-only, floating point
       Maximum and minimum current readings since last alarm/clear command.

VOLTAGE

       The  EDS0082  and  EDS0085  measure  voltage  in the 0-10V range, with upper and threshold
       limits and the ability to set an alarm and independently trigger a relay if the  value  is
       out of range.

   EDS0082/volts.[0-7|ALL] EDS0085/volts.[0-3|ALL]
       read-only, floating point
       Current voltage level. (0-10V)

   EDS0082/max_volts.[0-7|ALL] EDS0085/max_volts.[0-3|ALL]
   EDS0082/min_volts.[0-7|ALL] EDS0085/min_volts.[0-3|ALL]
       read-only, floating point
       Maximum and minimum voltage readings since last alarm/clear command.

THRESHOLD

       High  and  low range of acceptable sensor readings. Values outside this range will trigger
       an alarm if the corresponding EDS00XX/set_alarm flag is set.

   EDS00XX/threshold/temp_hi EDS00XX/threshold/temp_low
       read-write, floating-point
       Threshold temperatures in the specified temperature scale. Default Celsius.

   EDS006X/threshold/humidity_hi EDS006X/threshold/humidity_low
   EDS006X/threshold/dew_point_hi EDS006X/threshold/dew_point_low
   EDS006X/threshold/heat_index_hi EDS006X/threshold/heat_index_low
   EDS006X/threshold/humidex_hi tEDS006X/threshold/humidex_low
       read-write, floating-point
       Threshold humidity values.  Dew point and Heat index  are  in  the  specified  temperature
       scale. Default Celsius.

   EDS006X/threshold/pressure_hi EDS006X/threshold/pressure_low
   EDS006X/threshold/inHg_hi EDS006X/threshold/inHg_low
       read-write, floating-point
       Threshold  barometric  pressure values.  Pressure is the specified pressure scale. Default
       mBar.

   EDS006X/threshold/light_hi EDS006X/threshold/light_low
       read-write, unsigned
       Threshold light (lux) values.

   EDS0070/threshold/vib_hi EDS0070/threshold/vib_low
       read-write, unsigned
       Vibration sensor alarm limits in 0-1023 range.

   EDS007X/threshold/resistance_hi EDS007X/threshold/resistance_low
       read-write, floating-point
       Threshold RTD resistance values (Ohm).

   EDS0080/threshold/current_hi.[0-7|ALL] EDS0080/threshold/current_low.[0-7|ALL]
   EDS0082/threshold/volts_hi.[0-7|ALL] EDS0082/threshold/volts_low.[0-7|ALL]
   EDS0083/threshold/current_hi.[0-3|ALL EDS0083/threshold/current_low.[0-3|ALL]
   EDS0085/threshold/volts_hi.[0-3|ALL] EDS0085/threshold/volts_low.[0-3|ALL|]
       read-write, floating-point
       Voltage or current threshold limits

SET ALARM

       Set conditional alarm to trigger if corresponding flag is set. Also must set high and  low
       threshold.

   EDS00XX/set_alarm/temp_hi EDS00XX/set_alarm/temp_low
   EDS006X/set_alarm/humidity_hi EDS006X/set_alarm/humidity_low
   EDS006X/set_alarm/dew_point_hi EDS006X/set_alarm/dew_point_low
   EDS006X/set_alarm/heat_index_hi EDS006X/set_alarm/heat_index_low
   EDS006X/set_alarm/humidex_hi EDS006X/set_alarm/humidex_low
   EDS006X/set_alarm/pressure_hi EDS006X/set_alarm/pressure_low
   EDS006X/set_alarm/inHg_hi EDS006X/set_alarm/inHg_low
   EDS006X/set_alarm/light_hi EDS006X/set_alarm/light_low
   EDS0070/set_alarm/vib_hi EDS0070/set_alarm/vib_low
   EDS007X/set_alarm/resistance_hi EDS007X/set_alarm/resistance_low
   EDS0080/set_alarm/current_hi.[0-7|ALL|BYTE]
   EDS0080/set_alarm/current_low.[0-7|ALL|BYTE]
   EDS0082/set_alarm/volts_hi.[0-7|ALL|BYTE]
   EDS0082/set_alarm/volts_low.[0-7|ALL|BYTE]
   EDS0083/set_alarm/current_hi.[0-3|ALL|BYTE]
   EDS0083/set_alarm/current_low.[0-3|ALL|BYTE]
   EDS0085/set_alarm/volts_hi.[0-3|ALL|BYTE]
   EDS0085/set_alarm/volts_low.[0-3|ALL|BYTE]
       read-write, yes-no
       Flag to set corresponding out-of-range alarm. "1" turns on flag, and "0" turns off.

ALARM

       Show  or  clear the out-of-range flags. When set, the device will respond to a conditional
       search. Clearing the flags is performed with the  EDS00XX/alarm/clear  command,  not  just
       having the measured value return to the center range.

   EDS00XX/alarm/clear
       write-only, yes-no
       Write "1" to clear ALL the alarm flags.

   EDS00XX/alarm/temp_hi EDS00XX/alarm/temp_low
   EDS006X/alarm/humidity_hi EDS006X/alarm/humidity_low
   EDS006X/alarm/dew_point_hi EDS006X/alarm/dew_point_low
   EDS006X/alarm/heat_index_hi EDS006X/alarm/heat_index_low
   EDS006X/alarm/humidex_hi EDS006X/alarm/humidex_low
   EDS006X/alarm/pressure_hi EDS006X/alarm/pressure_low
   EDS006X/alarm/inHg_hi EDS006X/alarm/inHg_low
   EDS006X/alarm/light_hi EDS006X/alarm/light_low
   EDS0070/alarm/vib_hi EDS007X/alarm/vib_low
   EDS007X/alarm/resistance_hi EDS007X/alarm/resistance_low
   EDS0080/alarm/current_hi.[0-7|ALL|BYTE]
   EDS0080/alarm/current_low.[0-7|ALL|BYTE]
   EDS0082/alarm/volts_hi.[0-7|ALL|BYTE]
   EDS0082/alarm/volts_low.[0-7|ALL|BYTE]
   EDS0083/alarm/current_hi.[0-3|ALL|BYTE]
   EDS0083/alarm/current_low.[0-3|ALL|BYTE]
   EDS0085/alarm/volts_hi.[0-3|ALL|BYTE]
   EDS0085/alarm/volts_low.[0-3|ALL|BYTE]
   EDS0090/alarm/hi[0-7|ALL] EDS0090/alarm/low[0-7|ALL]
       read-only, yes-no
       Show  corresponding  out-of-range  alarm. "1" means in alarm state. Can only be turned off
       with clear

RELAY

       Optionally found on the EDS006X and EDS007X. Can be controlled by software  or  the  alarm
       condition.

   EDS00XX/relay/control
       read-write, unsigned
       Set the relay control scheme:

       0      alarm control with hysteresis

       1      alarm control but need EDS00XX/alarm/clear to unset

       2      Control with EDS00XX/relay/state

       3      Always off

   EDS00XX/relay/state
       read-write, yes-no
       Turn the relay on or off if the EDS00XX/relay/control is set to 2

LED light

       Found on the EDS006X and EDS007X. Can be controlled by software or the alarm condition.

   EDS00XX/LED/control
       read-write, unsigned
       Set the LED control scheme:

       0      alarm control with hysteresis

       1      alarm control but need EDS00XX/alarm/clear to unset

       2      Control with EDS00XX/LED/state

       3      Always off

   EDS00XX/LED/state
       read-write, yes-no
       Turn the LED on or off if the EDS00XX/LED/control is set to 2

COUNTER

   EDS00XX/counter/seconds
       read-only, unsigned integer
       Approximate seconds since power up.

   EDS0090/counter/pulses.0-7 | ALL
       read-only, unsigned integer
       Pulses  on  each  channel  since  power  up  or  reset.  Channel  should be set to input (
       EDS0090/output/set.x =0 )

   EDS0090/counter/reset.0-7 | ALL | BYTE
       read-write, yes-no
       Clear the pulse count on the corresponding channel.

   EDS007X/counter/samples
       read-only, unsigned integer
       Approximate samples since power up.

MEMORY

   memory
       read-write, binary
       96 bytes  of  memory.  Not  all  is  writable.  Access  to  EDS00XX  functions  is  better
       accomplished through the data fields, which expose all the chip features.

   pages/page.0 ... pages/page.2 pages/page.ALL
       read-write, binary
       Memory  is  split  into  3  pages  of  32  bytes each. Only page 2 is writable.  ALL is an
       aggregate of the pages. Each page is accessed sequentially.

   EDS008X/memory
       read-write, binary
       160 bytes of  memory.  Not  all  is  writable.  Access  to  EDS008X  functions  is  better
       accomplished  through the data fields, which expose all the chip features. The EDS008X has
       more memory than the other chips, so  a  separate  entry  in  the  sudbirectory  makes  it
       available.

   EDS008X/pages/page.0-4 EDS008X/pages/page.ALL
       read-write, binary
       Memory  is  split into 5 pages of 32 bytes each. Only page 5 is writable.  The EDS008X has
       more memory than the other chips, so a separate entry in the sudbirectory makes the  extra
       pages available.  ALL is an aggregate of the pages. Each page is accessed sequentially.

SUB-TYPE

   tag
       read-only, ascii
       Text description of the device. Up to 30 characters.

   device_type
       read-only, ascii
       Device name. E.g: "EDS0071"

   device_id
       read-only, unsigned
       Number corresponding to the hexadecimal type. E.g:
       EDS0071 -> 0x0071 -> 113 in decimal

STANDARD PROPERTIES

   address
   r_address
       read-only, ascii
       The entire 64-bit unique ID. Given as upper case hexadecimal digits (0-9A-F).
       address starts with the family code
       r  address  is the address in reverse order, which is often used in other applications and
       labeling.

   crc8
       read-only, ascii
       The 8-bit error correction portion.  Uses  cyclic  redundancy  check.  Computed  from  the
       preceding  56  bits of the unique ID number. Given as upper case hexadecimal digits (0-9A-
       F).

   family
       read-only, ascii
       The 8-bit family code. Unique to each type of device.  Given  as  upper  case  hexadecimal
       digits (0-9A-F).

   id
   r_id
       read-only, ascii
       The  48-bit  middle  portion  of the unique ID number. Does not include the family code or
       CRC. Given as upper case hexadecimal digits (0-9A-F).
       r id is the id in reverse order, which is often used in other applications and labeling.

   locator
   r_locator
       read-only, ascii
       Uses an extension of the 1-wire design from iButtonLink  company  that  associated  1-wire
       physical connections with a unique 1-wire code. If the connection is behind a Link Locator
       the locator will show a unique 8-byte number  (16  character  hexadecimal)  starting  with
       family code FE.
       If no Link Locator is between the device and the master, the locator field will be all FF.
       r locator is the locator in reverse order.

   present (DEPRECATED)
       read-only, yes-no
       Is the device currently present on the 1-wire bus?

   type
       read-only, ascii
       Part  name  assigned  by Dallas Semi. E.g.  DS2401 Alternative packaging (iButton vs chip)
       will not be distiguished.

ALARMS

       None.

DESCRIPTION

   1-Wire
       1-wire is a wiring protocol and series of devices  designed  and  manufactured  by  Dallas
       Semiconductor,  Inc.  The bus is a low-power low-speed low-connector scheme where the data
       line can also provide power.

       Each device is uniquely and unalterably numbered during  manufacture.  There  are  a  wide
       variety  of  devices,  including memory, sensors (humidity, temperature, voltage, contact,
       current), switches, timers and data  loggers.  More  complex  devices  (like  thermocouple
       sensors)  can  be  built with these basic devices. There are also 1-wire devices that have
       encryption included.

       The 1-wire scheme uses a single bus master and multiple slaves on the same wire.  The  bus
       master  initiates  all  communication.  The  slaves  can  be  individually  discovered and
       addressed using their unique ID.

       Bus masters come in a variety of configurations including serial, parallel,  i2c,  network
       or USB adapters.

   OWFS design
       OWFS  is  a  suite of programs that designed to make the 1-wire bus and its devices easily
       accessible. The underlying principle is to create a virtual filesystem, with the unique ID
       being the directory, and the individual properties of the device are represented as simple
       files that can be read and written.

       Details of the individual slave or master design are hidden behind a consistent interface.
       The  goal  is to provide an easy set of tools for a software designer to create monitoring
       or control applications. There are some performance enhancements  in  the  implementation,
       including  data  caching,  parallel  access  to  bus  masters,  and  aggregation of device
       communication.  Still  the  fundamental  goal  has  been  ease  of  use,  flexibility  and
       correctness rather than speed.

   EDS00XX Overview
       The  EDS00XX  sensors  are  a  family  of  devices  from  Embedded Data Systems.  Although
       provisional support for several types is included, only early EDS0071 has been tested with
       OWFS.

       The sensors all share the same 7E family code. They have the same first memory page layout
       with a text tag property that describes them, and a sub-type field giving  the  particular
       sensor.  The  data  properties shown in a directory listing will be specific to the sensor
       sub-type.

   EDS0071
       The EDS0071 (3) is a micro-processor  based  1-wire  slave  made  by  EDS  (Embedded  Data
       Systams).  Is  uses  a  high  accuracy and extended range RTD sensor to accurately measure
       temperatures.

   Memory
       The EDS00XX sensors are read and controlled by accessing parts of  their  on-chip  memory.
       Although  the  raw  memory  contents  are  exposed in the memory and pages fields, all the
       available functionality is best accessed by the other fields. In fact,  directly  changing
       memory will confuse OWFS.

   Relay and LED
       All  the  EDS00XX  sensors  have  an LED and optional relay. Both can be controlled either
       directly, or when the sensors reaches an alarm state.

ADDRESSING

       All 1-wire devices are factory assigned a unique 64-bit address. This address  is  of  the
       form:

       Family Code
              8 bits

       Address
              48 bits

       CRC    8 bits

       Addressing under OWFS is in hexadecimal, of form:

              01.123456789ABC

       where 01 is an example 8-bit family code, and 12345678ABC is an example 48 bit address.

       The dot is optional, and the CRC code can included. If included, it must be correct.

DATASHEET

       EDS0064 EDS0065 EDS0066 EDS0067 EDS0068
              https://docs.google.com/viewer?a=v&pid=explorer&chrome=true&srcid=0B_K3iXLLAI7vN2E4NGUwMGItMzc5MS00NDNmLTljZGYtN2NmM2Q3YWE5NmVh&hl=en

       EDS0070
              http://www.embeddeddatasystems.com/assets/images/supportFiles/manuals/EN-
              UserMan%20%20OW-Vibration%20V01.pdf

       EDS0071 EDS0072
              https://docs.google.com/viewer?a=v&pid=explorer&chrome=true&srcid=0B_K3iXLLAI7vMjVhNWQzYzItZTRhMi00NGY2LWI4NTQtYjZlYTgzYzY0NmNm&hl=en

       EDS0080 EDS0083
              https://eds.zendesk.com/attachments/token/ulnpj6mvpp6yzwo/?name=EN-USERMAN+OW-IO-
              AIX-420+v1p0.pdf

       EDS0082 EDS0085
              https://eds.zendesk.com/attachments/token/vyai6ylpw6edala/?name=EN-USERMAN+OW-IO-
              AIX-10V+v1p0.pdf

       EDS0090
              8 Discrete I/O

SEE ALSO

   Programs
       owfs (1) owhttpd (1) owftpd (1) owserver (1) owdir (1) owread (1)  owwrite  (1)  owpresent
       (1) owtap (1)

   Configuration and testing
       owfs (5) owtap (1) owmon (1)

   Language bindings
       owtcl (3) owperl (3) owcapi (3)

   Clocks
       DS1427 (3) DS1904 (3) DS1994 (3) DS2404 (3) DS2404S (3) DS2415 (3) DS2417 (3)

   ID
       DS2401 (3) DS2411 (3) DS1990A (3)

   Memory
       DS1982  (3)  DS1985  (3) DS1986 (3) DS1991 (3) DS1992 (3) DS1993 (3) DS1995 (3) DS1996 (3)
       DS2430A (3) DS2431 (3) DS2433 (3) DS2502 (3) DS2506 (3) DS28E04 (3) DS28EC20 (3)

   Switches
       DS2405 (3) DS2406 (3) DS2408 (3) DS2409 (3) DS2413 (3) DS28EA00 (3) InfernoEmbedded (3)

   Temperature
       DS1822 (3) DS1825 (3) DS1820 (3) DS18B20 (3) DS18S20 (3) DS1920 (3) DS1921 (3) DS1821  (3)
       DS28EA00  (3)  DS28E04  (3)  EDS0064  (3)  EDS0065 (3) EDS0066 (3) EDS0067 (3) EDS0068 (3)
       EDS0071 (3) EDS0072 (3) MAX31826 (3)

   Humidity
       DS1922 (3) DS2438 (3) EDS0065 (3) EDS0068 (3)

   Voltage
       DS2450 (3)

   Resistance
       DS2890 (3)

   Multifunction (current, voltage, temperature)
       DS2436 (3) DS2437 (3) DS2438 (3) DS2751 (3) DS2755 (3) DS2756 (3) DS2760  (3)  DS2770  (3)
       DS2780 (3) DS2781 (3) DS2788 (3) DS2784 (3)

   Counter
       DS2423 (3)

   LCD Screen
       LCD (3) DS2408 (3)

   Crypto
       DS1977 (3)

   Pressure
       DS2406 (3) TAI8570 (3) EDS0066 (3) EDS0068 (3)

   Moisture
       EEEF (3) DS2438 (3)

AVAILABILITY

       http://www.owfs.org

AUTHOR

       Paul Alfille (paul.alfille@gmail.com)